GV PK-12 AND PK-18
Will help you save energy, money and time while improving indoor air quality
Mediapak Modules
The GV PK-18 and PK-12 MediaPAK™ Modules will help you save energy, money and time while improving indoor air quality, removing odors and preventing corrosion. The specialty design features a durable, adhesive-free construction with highly aerodynamic airfoil screens, easy access sampling ports and the patented Posi-Track™ technology.
Improved Airflow Distribution: Our professional team of scientists and engineers have created an aerodynamic airfoil screen design. This enhancement provides a lower pressure drop, thus saving you energy costs.
Technical Specifications
| PK-18 | PK-12 | |
|---|---|---|
| Nominal size | 24" W × 6" H × 18" D (610 × 152 × 457 mm) | 24" W × 12" H × 12" D (610 × 305 × 305 mm) |
| Media volume | 0.5 ft³ (0.014 m³) | 1.0 ft³ (0.028 m³) |
| Filter medium bed depth | 1" (25.4 mm) | 3" (76.2 mm) |
| Pressure drop | Not to exceed 0.405 IWG @ 500 ft/min (101 Pa @ 2.54 m/s) | Not to exceed 1.20 IWG @ 250 ft/min (299 Pa @ 1.27 m/s) |
| Temperature | -4°F to 125°F (-20°C to 51°C) | -4°F to 125°F (-20°C to 51°C) |
Available media blends (commercial use): Jet & Diesel Exhaust Blend; Outdoor Pollution & Corrosion Blend; Kitchen Odor & Smoke Blend; Bathroom Odor & Ammonia Blend. The media uses chemisorption, which chemically converts contaminant gases into inert solids trapped inside the media, removing them permanently, unlike activated carbon.
Construction & Materials
- High Impact Polystyrene (HIPS) frame, 100% recyclable plastic
- Rigid frame that prevents bowing and air bypass
- Aerodynamic airfoil screens
- Each module packed on a media settling table to ensure a packed bed
- Built as two half units for easy lifting and installation
- Media is non-toxic and non-hazardous as supplied
Accessories
- GV engineered media blends (see above)
- Removable sampling port for media analysis
- QR-code product label linking to safety data sheets and product information
- Compatible with Purafil Side Access Units and existing module- or cassette-based housings
Certifications & Standards
- UL Classified (see complete marking on product)
- Manufactured under an ISO 9001 quality management system
- Pressure drop tested by an independent laboratory following ASHRAE Standard 52.2-2010 procedures
- Continuous operating temperature rated up to 125°F
Installation Recommendations
- Seat modules fully in the tracking so the tongue-and-groove notching and Posi-Track seal engage; no extra gasket is needed.
- Check the selected media blend’s temperature limits in its bulletin.
- Take a media sample through the sampling port to estimate replacement date.
- To recycle, discard spent media first, then take the empty module to a recycling facility; dispose of full modules per local, state and national regulations.